|
Let’s take a look on how to
tame power quality problems
Effort to minimize power quality problems in our increasing
microprocessor-based system starts by defining power quality and
understanding how to recognize it.
Exactly what is power quality? IEEE 1100, IEEE Recommended Practices for
Powering and Grounding Sensitive Electronic Equipment known as the
Emerald Book, defines it as powering and grounding sensitive electronics
equipment in a manner that is suitable to the operation of that
equipment. Another definition could be the degree to which the power
system affects the operation of electrical equipment. The user
generally grades power quality on the number and effects of problem they
have associated power system, real or otherwise. The more equipment
outages, erratic behavior, or damage, the worse the power quality.
Are all power disturbances real? The answer is no. This is not to say
that we don’t have power quality problems, but it is easy sometimes for
the layman or even the experienced to blame the power system for erratic
behavior or failures. It is also sometimes easy for a vendor, when put
on spot, to blame bad power for their machine’s failure to operate
properly. In many cases a careful investigation is needed to verify
that is was really a power quality problem.
What is good power quality? Most users would associate an ideal sine
wave with good power. What they want all the time. Unfortunately,
multiple exposures of power system both inside and outside of the
facility to transient, short, and long term events affects power
quality.
Sags, Swells, Surges, and
other Bad Actors
Now that we have defined good power quality and have some grip on its
boundaries, we need to define some of the common disturbances that can
create bad power quality. One of the problems is that a number of
different definitions exist for some event, which may lead to some
confusion. Following are some of more common power disturbances:
·
Sag:
Also known as dip, a sag is a reduction in RMS voltage at power
frequency for a duration of a half a cycle to a few seconds (IEEE 1100).
·
Swell: An increase in RMS voltage at power frequency from a half a cycle
to a few seconds.
·
Outage, transient, or dropout: A complete loss for a period of time.
·
Impulse, transient, or surge: A sub-cycle disturbance- a sharp, brief
discontinuity of the waveform of either polarity that may be additive or
subtractive to the normal waveform.
·
Oscillatory transient or ring wave: a sub-cycle disturbance that rings or
has the appearance of a decaying sine wave.
·
Notch: A switching or other disturbance of the normal power voltage
waveform lasting less than a half cycle. Initially opposite in polarity
to the normal waveform.
·
Under-voltage: A sustained low voltage, this is often called brownout,
though sometimes incorrectly. A brownout is an under-voltage, but not
all under-voltages are brownouts. A brownout is a sustained
under-voltage caused by a utility on purpose in time of heavy load.
·
Noise: Unwanted electrical signal in a circuit that produces unwanted
effects.
·
Harmonics: Multiple of the fundamental frequency that exist in a power
system due to nonlinear device operation
Noise and Harmonics
Power disturbances can originate from both inside and outside of a
facility. They can also be due to normal and abnormal activity in the
power system.
Normal activities that cause power disturbance are switching transients,
utility capacitor bank switching operation, starting and shutting down
of load equipment, arc welders, furnaces, adjustable-speed drives,
fluorescent lights, and the operation of nonlinear electrical
equipment. Common abnormal activities are faults, fault clearing, and
lightning. A poor grounding system can contribute substantially to bad
power quality.
Harmonics are an area of growing concern. We are increasingly installing
equipment with nonlinear switch mode power supplies, other nonlinear
devices, and variable-speed drives. Many facilities no longer have pure
sine wave power and this can cause detrimental effects.
One of the most touted problems is overheating of the neutral on
three-phase system, four-wire circuits feeding computer loads.
Harmonics also can cause overheating of transformers, premature
over-current device operation, metering problems, malfunction of
computer and sensitive electronic control boards, high crest factor, and
voltage distortion problems. For three-phase circuits, the odd
harmonics (3,5,7,…) can cause problems because they are negative
sequence (opposite in rotation sequence) to the fundamental.
The third and odd multiple of three (9th, 15th,
etc) commonly called the “Triplen” harmonics, cause problems because
they are in phase with the fundamental- rather than cancel in the
neutral, they add up, leading to potential overheating of the neutral if
it’s undersized. Harmonics are discussed in ANSI/IEEE standard 519,
“IEEE Guide for Harmonic Control and Reactive Compensations of Static
Power Converters”.
Noise in AC distribution system comes from high-frequency components that
are impressed on the 60 Hz wave. These can come from transients with
high-frequency components, from nonlinear devices, and from devices that
operate at high frequencies. High-frequency components tend to damp out
quickly due to the inductance in the wiring.
Another problem is AC noise coupled into or conducted in the DC side.
Bad grounding can cause AC and lightning transients to enter the DC side
with detrimental effects. Noise can affect communication circuits
through bad grounding techniques and exposure to noise sources. IEEE
standard 58, “IEEE Guide for the installation of electrical Equipment to
Minimize Electrical Noise Input to Controllers from External Sources”,
covers this subject extensively.
Band-Aid approach
As in many other control-related areas, the tendency with power quality
problems is to take Band-Aid approach: we fix what is biting us at the
time. But because power systems are interconnected and extend into
every corner of a facility, it’s important to evaluate the system as a
whole. We need to understand our equipment sensitivities, locate the
problem, and uncover the sources,
Our power systems are connected to external sources as well as
interconnected within the facility, so power quality problems from both
inside and outside can propagate throughout our system. The effect of
propagation depends on the size and duration of the disturbance and the
propagation path from the source to the equipment under concern. Since
our systems are constantly changing, a Band-Aid or partial solution
today may be inadequate tomorrow or may just shift the problem
elsewhere.
Do an Audit
A power quality audit takes a systematic, comprehensive look at the power
supply, the distribution system including grounding, the disturbance
spectrum, and the equipment you have connected to the power system. The
purpose of this audit is to identify current, potential, and future
vulnerabilities to power disturbances and to provide the basis for a
comprehensive protection scheme. It typically includes monitoring the
power supply and distribution system over a period of time with a power
monitor to get a baseline. Some companies install power –monitoring
equipment as part of their system for automated or semi-automated
collection of this data.
A power quality audit should include a comprehensive and systematic
visual and drawing inspection of the power distribution system and the
grounding system. If available, historical data can be collected from
any maintenance management system. Your utility may also be able to
provide pertinent information.
If you don’t have the expertise internally, or if you use external firm,
make sure you check them out, as doing a good power quality audit
requires a high level of expertise in electrical system and power
quality and not all firms that advertise this service can meet this
criterion. Remember, a process plant is in a constant state of flux with
equipment being removed, upgraded, replaced, and added. Future plans
must be taken into account when the audit is done. If not, you may
install more or less protection that you need, or the wrong protection
altogether.
Surge & The source of surge
Surges can be defined as a sub-cycle disturbance of an AC
waveform that is evidenced by a brief, sharp discontinuity of the
waveform. It is also known as a transient or impulse. Surges or
transients, while defined for AC, can also appear in DC power circuits
and digital communication circuits. Surges can cause damages to
equipment and the power system as well as cause equipment reset and
erratic behavior. Surges can also be cumulative, that is, a series of
surges can each do a little damage until a failure occurs.
Surges can originate from inside or outside the facility.
Some sources of surge inside your facility are internal faults, power
switching, ground transients, or caused by welding machines. Surges can
also come from outside sources including power line faults, utility
capacitor bank switching operation, lightning, and load switching by
transmission dispatch. Lightning and ground disturbance also can enter
a facility via paths other than the utility power lines, such as
lightning strikes within the facility and thundercloud movement. Phone
or communication lines may also propagate surges.
In general electromechanical devices can withstand voltage
surges until a dielectric breakdown occurs. The sensitive electronic
equipment, on the other hand, typically will have their operation upset
before a hard failure occurs. Electronic device susceptibility to
surges is often related to smaller geometries, line widths, and
component spacing in devices and circuits.
The move to switch-mode power supplies also has opened a
window of exposure because the older, linear power supplies were
basically low-pass filters, while a switch-mode power supply can act as
a high-pass filter. The move to high-speed digital circuits with 1’s
and 0’s has made such equipment susceptible to reset or erratic behavior
due to reference voltage and ground potential variation.
Surges can be normal or common mode. Normal mode, also
called transverse-mode, surges appear between any two power or signal
wires. Common-mode surges generally appear equally and in phase on each
power or signal line to ground. The mode of the surge can determine
what type of protection is required. Like many things, in order to
provide a comprehensive and standard protection scheme, we need to be
able to categorize surges. ANSI/IEEE Standard C62.41-1991,
“Recommended Practices for Surge Voltages in Low-Voltage AC Power
Circuits, “breaks down a facility into three categories or areas and
defines different type of surge waves with different characteristics for
each area. Three areas are: 1) service entrance and outside; 2)
mid-building, feeders and short branch circuits; 3) and long branch
circuits and receptacles. The impedance in your wiring system can also
have a natural effect of reducing propagating surges.
Note that once inside the building or facility, the voltage
test limit in the standard is 6kV, the voltage above which you will have
insulation breakdown and flashover in low-voltage power distribution
circuits.
Manufacturing facilities or processing plants many times are
more spread out than the “building” description in the standard and may
have a number of separately derived services. This spreading out is
generally physical or geographical and opens the system to transients
that originate from lightning or large-scale ground disturbances. This
can make providing a comprehensive protection scheme much more
difficult, particularly for remote areas such as tank farms and pipeline
stations.
Solutions 1: Dedicated Circuits
Now that we
have a grip on what surges are and where they come from, how do we
protect against them?
There is variety of protection devices and schemes available, ranging
from fairly inexpensive to expensive. Obviously, the money spent on
protection must be weight against the cost of the equipment and the cost
of any outages that might result from not having the protection. Risk
or consequences and probabilities may also be used as defining factor.
One means of providing some protection is to put sensitive equipment on
dedicated circuits. This is common but relatively expensive method. It
provides some isolation from other equipment and common connection and
uses the impedance in the wiring to reduce the exposure to internal
transients. It is not however, a cure-all as some surges can and will
propagate down dedicated circuits.
Solutions 2: Surge Suppressors
Probably the lease expensive device to protect against surges is the
transient-voltage surge suppressor (TVSS). ANSI/IEEE Standard
C62.41-1991 provides a basis for the selection of voltage and current
tests to be applied in evaluating surge withstanding capability of
equipment connected to utility power system, primarily residential,
commercial, and light industrial facilities. This standard provides the
basis for testing of TVSSs.
ANCI/IEEE C62.45, “Guide on Surge Testing for Equipment Connected to
Low-Voltage AC power Equipment” provides guidance on testing methods and
safety aspects for testing equipment connected to low voltage (1000volts
and less). Other ANSI/IEEE C62.xx series standards cover a range of
surge-related areas. UL Standard 1449-1998 (second edition), “UL
Standard for Transient Voltage Surge Suppressors” covers the UL
requirement for listing of permanently connected, cord-connected, and
direct plug-in TVSSs.
The tests performed for the listing requirement assigns a “Measured
Limiting Voltage” or suppression voltage rating that places the TVSS in
a UL voltage class. In addition, to the safety requirements, there is
an optional test for effectiveness and reliability of the TVSS. This
adjunct testing was requested of UL by Federal government and consists
of three grades (A, B, and C, wit A the best) that indicate endurance;
three classes (1, 2, and 3 with 1 being the best) that specify the
let-thru voltage; and two modes (1 or 2 with 1 meaning ground not
contaminated) that specify whether the ground is contaminated or not
during operation.
Be careful of statements like
“designed to meet” or “designed per”
You want the TVSS to be UL-listed or approved by some other national
recognized testing laboratory (NTRL), and you need to understand what
listing or approval means. If additional testing is advertised, it
should be done by an independent third party (independent is sometimes
hard to determine). Independent testing should have its basis in
ANSI/IEEE C62.41.
TVSSs come in many shapes and forms, some effective, some almost
useless. These are essentially three types: ones that shunt the surge
to the neutral and/or ground, ones that block the surge (series type)
and hybrids of the two.
The shunt types use three basic technologies: metal oxide varistors (MOV),
silicon avalanche diodes (SAD), gas discharge tubes, and combinations
thereof. Basically, MOVs are inexpensive, relatively fast, and appear
by themselves in cheap TVSSs, but have limited energy-handling
capability. MOVs are generally notorious for failure after repeated
surges, are typically fused, and should have a failure light or
indicator. If not, you may think you have the protection when you
don’t. They may also come with counter reading indicating the end of
life cycle.
Series TVSSs are generally an indictor or choke in series with the power
line combined with capacitors in parallel. TVSSs may also contain active
electronic element to provide protection.
TVSSs have two basic purposes: to protect the system and attached
equipment, and to keep the equipment operating satisfactorily during a
surge. These purposes can be in conflict in the design of a TVSS. A
shunt-type TVSS may provide protection but can not always prevent the
reset or erratic behavior of equipment due to contamination of ground
line or high neutral voltage. The series types block the surge but the
surge may find a lower-impedance path and cause damage elsewhere.
The hybrid TVSS is a combination of series and shunt elements that tries
to take the better of the two methods to provide both protection and
continued operation of equipment. TVSSs also come with bells and
whistles such as a light or buzzer to indicate failure or surge strikes,
fuse protection of MOVs, reset, and noise filters.
Experience proved that a single TVSS will not always provide adequate
protection. This gave rise to the cascade protection scheme, sometimes
called the zone, fortress, or staged method. In this scheme, two or
three levels of TVSS protection are provided: at the service entrance,
at the distribution panel, and at the load equipment, with each level
designed for a finer degree of protection as you approach the
equipment. Depending on the risk, the protection at the equipment may
involve other methods such as a power conditioner, isolation
transformers, or uninterruptible power supplies (UPS).
Solutions 3: Power
Conditioners
Moving up in cost and degree of protection against surges,
power conditioners are often used, generally at the equipment level to
keep the cost down. Common power conditioners include isolation
transformers, ferroresonant transformers, and combination of TVSS or
filter components and isolation transformers.
Isolation transformers provide good protection against
common-mode surges but limited protection against normal-mode surges.
Typical rating for common-mode reduction for isolation transformers are
80-140db (10.000-10,000,000 reduction). This reduction is also
frequency-dependent. Two other advantages to the isolation transformers
are that it helps block noise, and you will generally be deriving your
neutral closer to the equipment served, which minimizes neutral and
ground problems.
One bad thing is that the transformer does not provide any
voltage regulation against swells or sags. The shielding concept in
basic isolation transformers by placing an electrostatic shield between
windings reduces the effect of the capacitance between windings through
which transients might propagate.
A ferroresonant power conditioner uses magnetic saturation to
provide conditioning, and in addition to providing surge protection also
offers some voltage regulation ability. This type of conditioner has a
transformer designed so that the secondary is in magnetic saturation.
Changing the primary voltage or current does not change the magnetic
flux or secondary voltage. This type of conditioner can also reduce
normal-mode impulses. IT may, however be slow to respond to momentary
overload on the secondary side. They are generally about 90% efficient
but efficiency drops with load, which can cause them to run hot and make
audible noise. Ferroresonants may also interact negatively wit other
equipment downstream that has frequency elements.
Power conditioners also are available that combine
transformer with other protective elements. Some of these use isolation
or other transformer with TVSS elements or filter capacitors. These
also have the advantages of driving the neutral close to the equipment,
thus eliminating many of the effects of noise and transients from the
grounding system.
More on Noise &
Harmonics
Noise can come from high-frequency components of many of same
sources as surges. It can also come from electromagnetic interference
(EMI) introduced both by permanently installed equipment such as motors
and transformers and by temporary operations such as welding. In
general, the building wiring system naturally reduces noise with its
inherent impedance but some may propagate and cause problems.
Method to reduce noise includes shielding either the source or the target
of the noise and filtering or isolating the noise. Many of the devices
used for surge protection have built-in noise protection or filtering.
Common source of harmonics are switch-mode power supplies, fluorescent
lamps, and variable-speed drives. Harmonics combined with power
factor-correction capacitors can cause dangerous voltage levels in a
system due to resonant conditions. Some reports have been made of
overheating of the neutral in the buildings with a large number of
switch-mode power supplies. Many authors are also predicting that
utilities may impose large penalties on users with high harmonic
content, and user’s interest will certainly increase in this case.
Harmonics from variable-sped drives are generally minimized by installing
line reactors on the drive. These are also active types of harmonic
reducers available. Where these types of methods are not appropriate,
isolation transformers, oversized components, and K-rated
(harmonic-rated) transformers are used.
Power quality is not typically a simple subject related to a single area
in your facility, bus a system concern. There are many different types
of protection devices and schemes out there, some smoke and mirrors and
the rest valid methods. You must pick the right ones based on your
system, and the risk that you are willing to assume.
Uninterruptible Power Supply
(UPS)
A UPS, as its name implies, provides power in the event of
sustained outage. It stores power in batteries or a mechanical storage
element ender normal condition, then provide this power for a period of
time when utility power is lost. The supplied period of time can be
from a few seconds to a few hours, though the common time period ranges
from 15 minutes to an hour. Depending on the UPS configuration, it can
also provide a range of protection from power line disturbance such as
surges, noise, and distortion. UPSs come in three basic forms: Static,
Rotary, and Hybrid.
Static:
A static UPS has no moving parts. There are basically three
types of static UPS: off-line, line-interactive, and on-line. All of
these have batteries that determine the amount of power the UPS can
supply after normal power is lost. They recreate the sine wave output
using one of the two basic technologies pulse width modulation (PWM) and
steps (six step, 12 step, etc.). These recreations are not perfect any
may cause problem with the loads.
The total harmonic distortion (THD) as a percentage of the
output of the UPS can be a key selection parameter. A good UPS has a
THD of typically 3-5%. With the increase of harmonics in our system,
input THD may also be a consideration. The off-line UPS or standby
power supply (SPS) supplies utility power under normal conditions and
switches to battery backed-up inverter power upon power failure. The
main advantage of the off-line UPS us low cost, with other advantage
including smaller size, higher efficiency, and low operating time on
electronics,
Some of the disadvantages include limited surge and transient
protection, and since they pass the utility power thru under normal
conditions, they may also pass thru power line disturbances. They have
to switch to supply back up power, which may cause problem with some
loads, and you may not know if you have a problem until they fail on
demand. Battery maintenance may also be an issue, This type of UPS is
best suited for protecting small, stand alone equipment such as PCs and
peripherals.
The line-interactive UPS typically has a bi-directional
inverter and battery set that interacts directly with the incoming power
line, often thru a shared transformer. In the normal mode, the utility
power supplies the output power and charges the batteries. When utility
power is lost, the inverter/batteries supply the needed power thru the
shared transformer. This type of UPS has a control algorithm that turns
on the inverter when certain conditions are met.
The line-interactive UPS provides a good level of protection
at a medium cost. Some of the disadvantages are complex control scheme,
possible cycling of the inverter due to narrow voltage or frequency
window, and the possibility that you will not see a failure in the
inverter/batteries until they are demanded to supply power.
In the on-line UPS, also known as a dual conversion UPS, the
rectifier/inverter are online (supply power) under normal conditions.
IF utility power is lost, the battery and inverter supply power until
the batteries are exhausted. Some of the advantages of this type of UPS
are continuous regulated power output, higher system reliability, and
good diagnostics. Some of the disadvantages are higher costs, lower
efficiency, and larger size. This type of UPS commonly has a
maintenance bypass and a reserve power feed that can be switched online
thru a static, solid-state switch if the UPS output fails. With a
reserve power feed, consideration must be given to power conditioning
the reserve feed so that when operating on reserved feed, the effects of
power disturbances are minimized.
The online UPS is generally the most common static UPS for
highly critical, large loads in the process industries. It would not be
uncommon for this type of UPS to be used to supply a DCS, PLC, or other
instrumentation systems. In some cases, redundant arrangements of the
online UPS are used.
Rotary UPS:
The rotary UPS comes in several varieties but they typically
have a motor-generator combined with a static UPS, a DC motor, or a
mechanical energy storage element. Rotary UPSs are generally more
cost-effective in larger size; have high reliability; provide a clean,
unity, sine- wave output; and mechanically isolate the output from input
power. This provides complete elimination of power transients,
surges, brownouts, and blackouts up to the limit of the storage
element. Rotary UPSs also can provide voltage conversion and
frequencies other than 60Hz.
One type of rotary UPS is essentially a static UPS that
feeds a motor-generator. The advantages of this arrangement are the
inverter section can be made cheaper and more reliable, there is
mechanical isolation between input to output power, and the output is a
clean sine wave. The inverter can be online (powering the motor all the
time) or offline (powering the motor after power fails). An alternative
arrangement replaces the static UPS with a DC motor and battery set.
Another type of rotary UPS is the flywheel UPS. This type
comes in two basic varieties. One, the motor/flywheel/generator
arrangement, stores energy in a flywheel that continues to supply
rotating energy to the generator for a short period of time during an
outage, allowing the system to have the same benefit as a
motor-generator but also the ability to ride thru longer-duration sags.
In the second type, the flywheel storage element serves in place of the
traditional UPS battery. This type of UPS can ride through tens of
seconds even hundreds of seconds of outage.
Hybrid:
The hybrid UPS typically combines a motor-generator with a
standby generator. These types of UPS are commonly used in Europe and are beginning to be used in the U.S. The combination of a static switch and a standby generator
also creates a hybrid UPS.
A common variety is the diesel generator UPS, which is a
motor-generator that is also coupled to a diesel generator. The system
normally runs on motor-generator, but when the utility power fails the
motor continues to turn due to inertial effects, maintaining the power
while the diesel generator is started and come up to speed/frequency, it
is coupled to the motor shaft thus continuing the power to the load.
Synthesizer Summary:
A power synthesizer is used for a number of reasons and there
is wide variety to choose from. Some of the primary reasons are when
isolation is required, when a system must ride thru sustained sag or an
outage, when other frequencies are needed, and when a clean sine wave is
needed. Power synthesizers are a higher-cost solution but provide a
wide range of power quality solutions.
References
1.
IEEE Standard 1100-1992
2.
The Dranetz Field Handbook for Power Quality Analysis
3.
IEEE Standard 1346
4.
ITI (CBEMA) Curves & Application Note
5.
IEEE 581
6.
UL 1449 Adjunct Testing
7.
NEMA PE1-1992 |